Residual Current Circuit Breakers (RCCB)
Residual Current Circuit Breakers (RCCBs) protect against leakage currents.
Note
A Type B+ RCCB is not recommended; the high frequency sensitivity can trip the circuit breaker unnecessarily.
Caution
Do not use RCCBs to switch machines on or off.
EGYM machine | RCCB type | Required sensitivity | Machines per RCCB |
|---|---|---|---|
Smart Strength (eco II & Series 3) | Type A (AC and pulsing current- sensitive) RCCB | IΔN = 30 mA | Maximum 4 Applies to all models, including M9 Leg Press and M20 Squat |
EGYM eco I | Type B (DC-sensitive) CautionUsing unauthorized or incompatible RCCBs can compromise safety and increase the risk of electrical hazards. Tested and approved RCCBs:
| IΔN = 30 mA | Maximum 4 Applies to all models, including M9 Leg Press. |
Smart Flex | Type A (AC and pulsing current-sensitive) RCCB | IΔN = 30 mA | Maximum 8 |
Fitness Hub & Fitness Hub seca edition | The Fitness Hub does not require a separate RCCB. | ||
EGYM machine | RCCB type | Required sensitivity | Machines per RCCB |
|---|---|---|---|
Smart Strength (eco II & Series 3) | Type A (AC and pulsing current- sensitive) RCCB | IΔN = 30 mA | Maximum 4 Applies to all models, including M9 Leg Press and M20 Squat |
EGYM eco I | Type B (DC-sensitive) CautionUsing unauthorized or incompatible RCCBs can compromise safety and increase the risk of electrical hazards. Tested and approved RCCBs:
| IΔN = 30 mA | Maximum 4 Applies to all models, including M9 Leg Press. |
Smart Flex | Type A (AC and pulsing current-sensitive) RCCB | IΔN = 30 mA | Maximum 8 |
Fitness Hub & Fitness Hub seca edition | The Fitness Hub does not require a separate RCCB. | ||
EGYM machine | RCCB type | Required sensitivity | Machines per RCCB |
|---|---|---|---|
Smart Strength (eco II & Series 3) | Type A (AC and pulsing current- sensitive) RCCB | IΔN = 30 mA | Maximum 4 Applies to all models, including M9 Leg Press and M20 Squat |
Fitness Hub & Fitness Hub seca edition | The Fitness Hub does not require a separate RCCB. | ||
EGYM machine | GFCI type | Required sensitivity | Machines per GFCI |
|---|---|---|---|
Smart Strength (eco II & Series 3) | Type A (AC and pulsing current- sensitive) | IΔN = 30 mA | Each machine requires a separate Class A GFCI (ground fault circuit interrupter) outlet or circuit breaker. |
Fitness Hub & Fitness Hub seca edition | The Fitness Hub does not require a separate GFCI. | ||